Página 1 - Liebert XDV

Precision CoolingFor Business-Critical Continuity™Liebert XDV™User Manual–50 & 60 Hz

Página 2 - SAVE THESE INSTRUCTIONS

General product information43.3 Equipment InspectionUpon arrival of the unit, and before unpacking, verify that the labeled equipment matches the bill

Página 3 - TABLE OF CONTENTS

General product information53.3.2 Unit HandlingIf possible, transport the unit using a forklift or pallet jack.• If using a forklift or pallet jack, e

Página 4

General product information6Export Packaging1. Unbend all metal tabs as indicated in Step 1 in Figure 6.2. Remove outer packaging when ready to instal

Página 5

General product information7Removing the Liebert XDV from the Pallet1. Unfold the unit bag to expose the Liebert XDV.2. Verify the nameplate informati

Página 6

Mechanical Considerations84.0 MECHANICAL CONSIDERATIONS4.1 Determining Placement in the Conditioned SpaceLiebert XDVs should be placed above or on top

Página 7 - XD V B K —

Mechanical Considerations94.2 Changing the Air Intake LocationThe Liebert XDV comes from the factory with the air intake on the rear of the unit. If r

Página 8 - 2.0 INSTALLATION

Mounting the Liebert XDV105.0 MOUNTING THE LIEBERT XDVThe Liebert XDV module must be securely attached to the top of the computer cabinet or, alterna-

Página 9 - XDH , XDO or XDV

Mounting the Liebert XDV11Figure 11 Mounting hole locations—standard mounting methodFigure 12 Mounting hole locations—alternate mounting pointsFan tra

Página 10 - 3.3 Equipment Inspection

Mounting the Liebert XDV125.1.2 Using Supplied Clips for Mounting1. Attach the mounting clips to the back of the Liebert XDV by fitting them into the

Página 11 - Domestic Packaging

Mounting the Liebert XDV135.2 Suspended Mounting MethodThe Liebert XDV also may be mounted above the cabinet by suspending it either from overhead com

Página 12 - Export Packaging

GENERAL SAFETY GUIDELINESSAVE THESE INSTRUCTIONSFluorinated Greenhouse Gas Requirements—European UnionStationary air conditioning, refrigera

Página 13 - Removing the Liebert XDV

Mounting the Liebert XDV145.2.1 Suspending the Liebert XDV from UnistrutsThe Liebert XDV may be bolted to customer-supplied Unistruts. The height of t

Página 14 - 4.0 MECHANICAL CONSIDERATIONS

Mounting the Liebert XDV15Figure 16 Suspending Liebert XDV from the overhead structure3/8"-16 all-thread bolts,field-supplied, typicalTo prevent b

Página 15 - Mechanical Considerations

Mounting the Liebert XDV165.3 Mounting Liebert XDVs in Stacked SetupLiebert designed the Liebert XDV to permit mounting the units in a stacked arrange

Página 16 - 5.0 MOUNTING THE LIEBERT XDV

Mounting the Liebert XDV175.3.1 Hanging Stacked Liebert XDVs from UnistrutsBecause the upper Liebert XDV in a stacked arrangement must be positioned f

Página 17 - BOTTOM VIEW

Mounting the Liebert XDV185.3.2 Hanging Stacked Liebert XDVs from the Overhead StructureBecause the upper Liebert XDV in a stacked arrangement must be

Página 18 - Mounting the Liebert XDV

Piping196.0 PIPING6.1 European Union Fluorinated Greenhouse Gas RequirementsStationary air conditioning, refrigeration, heat pump equipments and stati

Página 19 - 5.2 Suspended Mounting Method

Piping20Figure 22 Typical Liebert XDV piping—non-interlaced connection6.2.1 Piping Connections to Liebert XDP or Liebert XDCRefer to site specific dra

Página 20

Piping21Figure 23 Hard-piped connection diagramCopper TubingTotal length of eachline from Liebert XDV to Main; not to exceed 72" (1829mm)Top of

Página 21

Piping226.4 Hard Piped Connection SizesSupply piping connection is 1/2" OD copper pipe and return piping connection is 5/8" OD copper.6.4.1

Página 22 - For details on preventing

Piping23Figure 25 Schrader valve location for venting holding charge6.4.2 Brazing Preparations—Hard-Piped UnitsAfter the holding charge for a hard-pip

Página 23

iTABLE OF CONTENTSGENERAL SAFETY GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER1.0 LIEBERT XDV C

Página 24

Piping246.6 Connection Methods—One-Shot ConnectionsThe assembly and connection means used for piping in the Liebert XD system are the same as those us

Página 25 - 6.0 PIPING

Piping256.6.1 Refrigerant Charge—Pre-Charged OptionLiebert XDVs with the pre-charged option are equipped with one-shot connections on the supply and r

Página 26

Piping266.9 Connecting a Liebert XDV with Liebert Flex Pipe to an Operational Liebert XD SystemNOTICEBefore connecting the Liebert XDV with Liebert Fl

Página 27 - Refer to Table 4 for details

Piping27Figure 29 Detail view of Liebert XD Flex Pipe and prefabricated piping port8. Repeat Steps 6 and 7 for the smaller coupler (supply line).9. O

Página 28 - Top View of

Piping286.10 Disconnecting a Liebert XDV With Liebert Flex Pipe From a Liebert XD SystemNOTICEBefore uninstalling a Liebert XDV with Liebert Flex Pipe

Página 29 - 6.5 Recommended Piping Size

Piping29Figure 32 Piping mains without Liebert XDV and Liebert Flex Pipe11. Repeat Steps 8 through 10 for the return coupler (larger coupler).12. Care

Página 30 - Detail “A”

Electrical307.0 ELECTRICALThe unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial tag for electrical req

Página 31 - Connection

Electrical31Figure 34 Liebert XDV electrical connections for CE-approved unitsPRIMARYPOWERSOURCESECONDARY82 8360Hz MODELS ONLY.FIELD WIRINGCONNECTIO

Página 32 - Tools Required

Electrical327.2 Connecting Low Voltage Wiring—OptionalLow voltage connections to the Liebert XDV are available only on units with the optional condens

Página 33

Installation Checklist and System Fill for Startup338.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP8.1 Checklist for Proper Installation___ 1.

Página 34

ii6.8 Connecting Liebert XD Flex Pipe to Liebert XDV Modules. . . . . . . . . . . . . . . . . . . . . . . . . . 256.9 Connecting a Liebert XDV with L

Página 35 - 6.11 Insulation

Operation349.0 OPERATIONThe Liebert XDV’s fan controls are on the front of the unit, near the fans, for easy access. Each switch controls the operatio

Página 36 - 7.0 ELECTRICAL

Maintenance3510.0 MAINTENANCEMinimal maintenance is required to keep the Liebert XDV operating at optimal levels. The unit should be cleaned and check

Página 37 - SECONDARY

Maintenance3610.2.1 Accessing Internal Electrical Components1. Disconnect all power inputs.2. Remove five screws to remove the front electrical panel

Página 38 - Rear View of Liebert XDV

Maintenance37To remove the fan tray:1. Remove the front electrical panel cover as described in 10.2.1 - Accessing Internal Electrical Components.2. Di

Página 39

Specifications3811.0 SPECIFICATIONSTable 5 Liebert XDV10 specificationsModelsXDV10BK--*; XDV10DK--*XDV10BKP-*; XDV10DKP-*XDV10BK-E*; XDV10DK-E*XDV10BK

Página 40 - 9.0 OPERATION

Specifications39Table 6 Liebert XDV8 specificationsModelsXDV8BK--*; XDV8DK--*XDV8BKP-*; XDV8DKP-*XDV8BK-E*; XDV8DK-E*XDV8BKPE*;XDV8DKPE*XDV8BKR-*; XDV

Página 41 - 10.0 MAINTENANCE

Specifications40Table 7 Liebert XD Liebert Flex Pipe assemblies, supply and returnDescriptionLiebert P/NStraight ConnectionAssemblyLiebert P/N90-Degre

Página 43 - Screws, 5

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Página 44 - * = Revision level of unit

iiiFIGURESFigure 1 Liebert XDV component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 46

Liebert XDV Component Locations and Model Number Nomenclature11.0 LIEBERT XDV COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATUREFigure 1 Liebert XDV co

Página 47

Installation22.0 INSTALLATION2.1 ReferencesThis document must be used together with site specific documentation and documentation for other parts of t

Página 48

General product information33.0 GENERAL PRODUCT INFORMATION3.1 Product/System DescriptionThe Liebert XDV cooling system is designed to be attached to