23
Battery Run Times
AGENCY
Safety EN 50091-1; CE low voltage directive; TUV Certificate
Surge EN61000-4-5, Level 3, Criteria A
ESD EN61000-4-2, Level 3, Criteria A
Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient/Burst
EN61000-4-4, Level 4, Criteria A
Emissions EN 50091-2, Class B; CE EMC directive
Conducted Immunity EN61000-4-6, Level 3, Criteria A
Harmonics EN61000-3-2
Flicker EN61000-3-3
Transportation ISTA Procedure 1A
Load % 500VA 650VA
5 156 192
10 113 95
20 49 42
30 31 30
40 22 21
50 17 14
60 11 13
70 9 10
80 7 7
90 5 6
100 4 5
NOTE
Approximate discharge times are in minutes and at 25°C
(77°F) with a resistive load.